10kV Short Circuit Current Limiter

Date: 2018-04-28 Views: 55


DDX1-12 Rated electrical parameters of products:

number

Parameter name

Unit

Technical Data

1

Rated voltage

kV

12

2

Rated current

A

630-6300

3

Rated pre-expected short-circuit breaking current

kA

50-200

4

Current limit coefficient = cut-off current / the peak Value of Pre-expected Fault Current

%

15~50

5

Insulation level

Power frequency withstand voltage

kV/1min

42

Lightning impulse withstand voltage

kV

75

Product Characteristics and advantages

◆ Strong short-circuit breaking capability ( large capacity ): rated breaking short-circuit current is 50kA~200kA

◆ Breaking speed is fast ( high speed ) :Total breaking duration:<10ms

◆ The breaking process has obvious current limiting characteristics ( current limiting )

◆ The action criterion adopts current instantaneous value and current change rate instantaneous value

◆The current sensor is integrated with the fast-speed disconnector, and the structure is simplified

◆ The electronic controller works independently in three phases through high temperature and strong interference tests to ensure the overall reliability of the product.

Product Usage

◆ Bypass current limiting reactor (energy saving, consumption reduction, reactive power elimination and power supply quality improvement)

◆ Parallel operation of sectionalized buses in large-capacity distribution system (optimizing load distribution and reducing network impedance)

◆ Short circuit protection of generator outlet or transformer low voltage side

◆ Short - circuit Protection of Branch Busbar and High Voltage Transformer in Power Plant