Menu

35kV Short Circuit Current Limiter

Date: 2018-04-25 Views: 32



DDX1-12 Rated electrical parameters of products:

number

Parameter name

Unit

Technical date

1

Rated voltage

kV

40.5

2

Rated current

A

630-6300

3

Rated pre-expected short-circuit breaking current

kA

50-200

4

Current limit coefficient = cut-off current / the peak Value of Pre-expected Fault Current

%

15~50

5

Insulation level

Power frequency withstand voltage

kV/1min

95

Lightning impulse withstand voltage

kV

185

Product features and advantages

Strong short-circuit breaking capability ( large capacity ): rated breaking short-circuit current is 50kA200kA

Breaking speed is fast (High speed): Total breaking duration:<10ms

The breaking process has obvious current limiting characteristics (Current limiting)

The action criterion adopts current instantaneous value and current change rate instantaneous value.

The current sensor is integrated with the fast-speed disconnector, and the structure is simplified

The electronic controller works independently in three phases through high temperature and strong interference tests to ensure the overall reliability of the product.

Product Usage

 Bypass current limiting reactor (energy saving, consumption reduction, reactive power elimination and power supply quality improvement)

 Parallel operation of sectionalized buses in large-capacity distribution system (optimizing load distribution and reducing network impedance)

Short circuit protection of generator outlet or transformer low voltage side

 Short - circuit Protection of Branch Busbar and High Voltage Transformer in Power Plant


Related recommendations
Copyright ©2018 - 2019 陕西蓝河电子工程有限公司版权所有.All Rights Reserved 犀牛云提供企业云服务