Application Scheme of DDX1 Short Circuit Current Limiter in Contact line
DDX1 short-circuit limiter is equivalent to a short-circuited busbar while it is up and running, load current flows through at this moment. When the short circuit fault happens in the feeder lines, the short-circuit current iz flowing through the feeder is the sum of the short-circuit currents provided by # 1 and # 2 transformers, ie. iz=i1+i2, which far exceeds the breaking capacity of the feeder breaker. After the DDX1 short-circuit current limiter is installed on the contact line, it can be cut off instantly within 3 ~ 5 ms. It contributes to the separate operation of two-section buses and reduce the short-circuit current by about 50% caused by the feeder switch.So, the short-circuit current i1 ( or i2 ) provided for only one transformer could be controlled within the safe range of the feeder switch. ( For the structure and principle of DDX1 short-circuit limiter, please refer to its specification ). The electrical diagram of the short-circuit current limiter after ...